MECCALTE BATTERY CHARGER MAS2024R

MECCALTE BATTERY CHARGER MAS2024R

Product Features:

INPUT SPECIFICATION 

Voltage range, VI:100 - 264V AC 

Frequency :47 - 63Hz 

Input current :5.5A max.

Leakage current :<2mA / 240VAC 

OUTPUT SPECIFICATION 

Voltage / Current:24.0V Nominal:20A Other voltages on request 

Ripple and noise :±0.5% 

Line regulation :±0.5% 

Load regulation:±1.0% 

Efficiency :Up to 92% 

Overload protection :Constant current limit 

Over temp. protection :Output shutdown with automatic recovery 

Reversed battery
protection :Automatic protection.
Disabled when in PSU mode. 

ALARMS AND LEVELS 

DC output voltages :Float = Factory set to 27.6V.
Boost (Bulk/Absorb) = Float Voltage +4%. 

AC / charger fail :Loss of AC input or DC output voltage control 

Low DC voltage alarm :Float voltage -12% alarm, -8% Reset 

High DC voltage alarm :Float voltage +7% alarm, +5% Reset 

Over voltage protection :30.5 Instantaneous lockout 

Battery disconnected :Open circuit on DC output (Disabled in PSU mode)

ISOLATION 

Withstand voltage :Input - Output, Input - Earth 1.5kV AC 

Isolation resistance :Input - Output, Input - Earth, Output - Earth
500V DC / 100M Ohms 

ENVIRONMENTAL SPECIFICATION 

Working temperature :-10ºC to +50ºC 

Working humidity :20 - 90% 

RH
Storage temperature :-20ºC to +85ºC 

Storage humidity :10 - 95% RH 

Unpacked weight :1.7 kgs

ORDERING INFORMATION 

Model No. :MAS 2024R

DC output :24V-20A 24V 20A

SmartCharge Automatic battery chargers provide a cost effective solution to most industrial battery charging requirements. Utilising the latest high efficiency switch-mode technology and microprocessor control, the SmartCharge 500-LC is suitable for charging most sealed or flooded batteries and is easily calibrated by the end user to suit the battery type. The multi-stage intelligent charging characteristic ensures accurate and efficient battery charging and is designed for permanent connection to the batteries maintaining them in a fully charged condition without overcharging. The SmartCharge 500-LC is fully protected against overload, reverse battery connection, over voltage and over temperature.

FEATURES 

• Cost effective 

• Micro-processor control 

• Small footrint & compact size 

• Din rail mounting 

• Automatic multi-stage charging 

• Manual boost override 

• Continously rated 

• Protections - Short circuit and overload - Over voltage - Over temperature - Reverse battery 

• Universal AC input range 

• Low ripple output 

• Naturally cooled 

• Simple calibration procedure 

• Comprehensive alarm monitoring 

• Fail alarm contact set

APPLICATIONS 

• Standby & prime power generators 

• Engine driven pumps and compressors 

• Switch gear tripping 

• Industrial control systems 

• Robust PSU 

• Alarm systems 

• Navigational aids

FINISH 

Aluminium / RAL9005 black fine texture 

FAIL ALARM RELAY CONTACT SET (OPTIONAL) 

Volt-free form C relay contact set for signalling of a fault alarm condition. The relay contacts de-energise 60 seconds after a fault occurs. The over voltage protection shutdown alarm de-energises the contacts instantly. 

TERMINATION 

AC input and DC output: 

Connections terminate to rising clamp screw terminals and will accept 6.0mm2 stranded cable. 

Optional fail alarm: 

Connections terminate to rising clamp screw terminals and will accept 2.5mm2 stranded cable. 

Connector ‘C1’ (signals): 

Pins 7 and 8 should be linked when the charger should also function as a PSU. 

NOTE: Reverse battery and battery disconnected alarms are disabled in PSU mode. 

The remaining pins are for expansion modules, communication interfaces, firmware upgrade, etc and should not be used.