Product features:
2V/24V voltage selection, using imported high-quality DIP, making it more reliable
Stable, easy to switch for selection
Switching power supply structure, wide AC input voltage range, small size, light weight, high efficiency.
Use multi-stage charging method (constant voltage, constant current, trickle float, complete stop)
Automatic charging, full charging according to battery charging characteristics prevent
The lead-acid battery can be overcharged to maximize the battery life.
With flow, short circuit, reverse polarity protection.
With charging fault alarm output function (passive relay contact), more convenient and safer
Charging voltage and current values can be adjusted in the field by potentiometer.
BOOST BOOST function, short boost port can boost 1.0V output voltage, with compensation
For winter charging discontent, as well as better use on old batteries.
Suitable for 24V battery pack with rated charging current of 3A.
Suitable for 12V battery pack with rated charging current 6A.
Charging status LED indicator: power indicator (green), charging indicator (red), full light off.
Depending on the characteristics of the battery charger, a two-stage charging method is used. The first stage is "constant current mode", that is, before the battery terminal voltage is lower than the preset value, the charge is constant current charge; The second is the "floating charge mode", that is, when the terminal voltage of the charger is higher than the preset value, the charging current decreases with the increase of the terminal voltage of the charger, and then the charge is floating charge. When the charging current is less than 0.5A, the terminal voltage gradually rises to a preset constant value, and the battery has been basically full (the charging indicator light is off), then the charging current will only offset the self-discharge of the battery, even if the charging time is long and harmless, that is, the charger can remain full and ensure the service life of the battery.
Category | Project | Specification | |
Input Characteri stic | nominal AC input voltage range | AC (100~240)V | |
Max. AC input voltage range | AC (95~280)V | ||
AC frequency | 50 Hz/60 Hz | ||
No-load power consumption | <3 W | ||
efficiency | AC 110 V | AC 220 V | |
>82% | >86% | ||
Max. input active power | LBC 2403 | LBC 1206 | |
130 W | 130 W | ||
Max. Input current | 2.5 A | 2.5 A | |
Output Characteri stic | No-load output voltage | 27.6 V,error ±1% | 13.8 V, error ±1% |
rated charging current | 3 A,error ±2% | 6 A,error ±2% | |
rated output | 85 W | 85 W | |
Alarm Output | relay contact | 0.5 A/250 VAC(Only useful with B suffixes, such as LBC2403B) | |
Insulating Property | insulating resistor | Input and output,input and shell both read DC500V 1min RL more than 500MΩ | |
insulating voltage | Input and output,input and shell both read AC1500V 50Hz 1min leak current IL Less than 3.5 mA | ||
Working Situation | working temperature | (-30~55)°C | |
store humidity | (-40~85)°C | ||
working humidity | 20% RH~ 93% RH( no condensation) | ||
storage humidity | 10% RH~ 95% RH(no condensation) | ||
weight | 0.63 kg | ||
Configurat ion | size | 138mm×90mm×53mm (length× width× height) |
The LBC series battery charger is a charger that uses the latest switching power program, and
Designed specifically for the charging characteristics of lead-acid batteries, suitable for engine starting
For long-term recharge (floating) lead-acid batteries, you can choose the right one
According to the selection table.