Product Description
Features of EA63-7D /AEC42-7/EA42-7 AVR
Sensing Input
Voltage 220 ~ 252 VAC ± 10%, 1 phase
Frequency 50 / 60 Hz selectable
Power Input:Voltage 200 ~ 260 VAC ± 10%, 1 phase 2wire Frequency 50 / 60 Hz
Output
Voltage: Max. 42 VDC
Current: Continuous 7A;Intermittent 15A for 10 sec
Resistance: Min. 6 ohm Max. 105 ohm
Voltage Regulation:<± 1 % ( with 4% engine governing )
Voltage Build-up
Residual voltage at AVR terminal: > 5 VAC
Voltage Adjustable Range:180 ~ 277 VAC
Thermal Drift:0.05% per °C change in AVR ambient
External Volts Adjustment:± 1 0% with 1 K ohm 1 watt trimmer
EMI Suppression:Internal electromagnetic interference filtering
Unit Power Dissipation:Max. 20 watt
Under Frequency Protection (Factory Setting)60 Hz system presets knee point at 55 Hz50 Hz system presets knee point at 45 Hz
Over Excitation Shutdown:Field volts shut down after a time delayIf exciter field volts exceed 52 ± 2 VDC
Quadrature Droop:Max. Sensitivity 1 VAC 2%Max. Input 5 VAC @ 5 ohm Burden
Dimensions: 140mm L * 125mm W * 79.4mm H
Weight : 680g ± 2%